Can I splice behind drywall with or without an electrical box?
|
You may not conceal any electrical splice. All electrical splices or wiring modifications must be contained in an approved electrical enclosure that is… © By: Dave Rongey |
Electrical Question from Robert about 220 Volt Wiring Splices
[ad#block]Question: Can I splice behind drywall with or without an electrical box for a 10 gauge dryer circuit wire using a Tyco cpgi-hs-slice-kit-uf, UL E91151 and be within code?
Thanks
Dave’s Reply:
Thanks for your electrical question.
Hi Robert – No, you may not conceal any electrical splice. All electrical splices or wiring modifications must be contained in an approved electrical enclosure that is accessible. This can be a junction box that has a blank cover placed on it as long as it is accessible from either side of a wall or accessible within an attic, crawl space or basement area. The only exception applies to direct burial cables where approved splicing methods are used.
The Following links will assist you with your electrical question:
Electrical Codes
For more information about 220 Volt Wiring Diagram
220 Volt Wiring Diagram
This link is helpful as a Homeowner
Do-It-Yourself Electrical
Make sure not to miss these Resources for: How-To-Videos
Electrical Videos
Be Careful and Be Safe – Never Work on Energized Circuits!
For Best Results Consult a Licensed Electrical Contractor.
Locate An Electrical Contractor in Your Area
The following may also be helpful for you:
|
Be Careful and Be Safe - Never Work on Energized Circuits!
Consult your Local Building Department about Permits and Inspections for all Electric Wiring Projects.
More articles about Electrical, Electrical Code NEC and Home Electrical Wiring: |
|
« Previous | Next » |
You Can Control Anything Using X-10 Devices! |
How do I wire power to more than one light switch? |
I Disagree – According to the National Electrical Code this is not true:
NEC 110-14 & 300-15 All splices, including ground wires, shall be made with an approved splice cap or “wire nut” and shall be made in approved electrical boxes or enclosures.
NEC 314.19 Wiring Methods junction boxes accessible Junction boxes shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building.
Tyco tap and splice kits are rated for concealment in remodeling applications
*** See my reply