Electrical Codes for Electrical Service Panels

Electrician Training Electrical Certification wiring recessed light fixtures Electrical Wiring Electrical Troubleshooting and Electrical Repairs wire outdoor light fixture Home Electrical Wiring Diagrams
wiring home generator and transfer switch wiring a 220 volt range cord outlet Wiring for GFCI Outlets Wiring Outlets and a Switched Outlet Wiring and Installing Ceiling Fans and Remote Controls wire dimmer switch wiring diagrams for switches wiring a dryer cord and 220 outlet circuit breaker panel
Electrical Wire and Cable

Electrical Codes for Electrical Service Panels

electrical-codes-for-panels Summary:
Listing of electrical codes for services with examples of electrical services codes for home electrical wiring.

Electrical Code Definitions for Home Electrical Service Panels


Understanding the Importance of Electrical Codes for Home Electrical Services

Primary Cause of Failures:

NEC 110.3
Written Electrical Correction - All locations
Failure to read the manufacturer's instructions.

NEC 110.3
Electrical equipment Equipment Listing and Labeling All electrical equipment, including luminaires, devices and appliances used as part of or in connection with an electrical installation shall be listed and labeled by a Nationally Recognized Testing Laboratory (NRTL) as having been tested and found suitable for a specific purpose;


Code Adoption Information: The codes shown are examples only and may not be current or accurate for your application or jurisdiction. Contact your local building authority for complete information.

NATIONAL ELECTRICAL CODES



NEC 110-3 and 110-14 Anti-Oxidant Compound shall be used on all aluminum conductor terminations.

NEC 110-26 The Depth of Working Space in the direction of access to live parts, when the voltage to ground does not exceed 150 volts, shall be a minimum of 3 feet. The minimum width of working space in front of electrical equipment shall be the width of the equipment or 30 inches, whichever is greater. This workspace shall be clear and extend from the floor to a height of 6 1/2 feet, and shall not be used for storage. All workspaces shall be provided with illumination.

NEC 230-8 and 230-54 Service Entrance Conduits shall be rain tight, arranged to drain, and sealed to prevent moisture condensation. Conductor Sizes for 120/240 Volt Single-Phase Dwelling Services
NEC 310-15 Copper Aluminum Service Rating
..............4 AWG......2 AWG ..100 amps
..............1 AWG..........2/0.... 150 amps
.................2/0............ 4/0..... 200 amps
Consult the conductor insulation type to determine the exact service rating.

NEC 230.54 Electrical Services - Service entrance raceways shall be rain-tight and arranged to drain.


NEC 230.70 Electrical Services - The service disconnecting means shall be installed at a readily accessible location either outside a building or structure or inside nearest the point of entrance of the service entrance conductors.

NEC 240-3 The rating of the fuse or circuit breaker generally determines the minimum size of the circuit conductor, per the following table:
Minimum Wire Size Fuse or Circuit
Breaker Size Copper / Aluminum
15 amp ..........14... n/a
20 amp ..........12... n/a
30 amp ..........10.... 8
40 amp ...........8.... 6
50 amp ...........6.... 4
Note: Conductors that supply motors, air conditioning units, and other special equipment may have overcurrent protection that exceeds the general limitations in the above chart.

NEC 240-24 Electrical Panels shall be readily accessible and shall not be located in bathrooms or in the vicinity of easily ignitable materials such as in clothes closets.

NEC 300.4 Electrical Services Conduit raceways "Where raceways containing ungrounded conductors No. 4 or larger enter a cabinet, box, or enclosure, the conductors shall be protected by a bushing providing a smoothly rounded insulating surface.

NEC 300-5 Underground Service laterals shall have their location identified by a warning ribbon that is placed in the trench at least 12 inches above the underground installation.

NEC 300.5 Underground Wiring conduits and raceways "Direct buried cable or conduit or other raceways shall meet the following minimum cover requirements:
Direct Burial Cable Rigid or Intermediate Metal Conduit Non Metallic Raceway (PVC)
24 inches 6 inches 18".
Residential branch circuits rated 20 amps or less at 120 volts or less and with GFCI protection at their source are allowed a minimum cover of 12".
NOTE: This table does not apply to underground wiring for outdoor pools, spas, or hot tubs - see NEC Article 680.

NEC 300.7 Electrical Services Wire Conductors Portions of raceways or sleeves subject to different temperatures (i.e. passing from the interior to the exterior of a building) shall be sealed with an approved material to prevent condensation from entering equipment.

NEC 300.9 Electrical Services Conduit raceways The interior of raceways installed in wet locations above grade shall be considered wet locations.

NEC 310-15 Electrical Services wire conductor sizes "CONDUCTOR SIZES FOR 120/240 VOLT 3-WIRE, SINGLE-PHASE, DWELLING SERVICES AND FEEDERS
Copper -- Aluminum -- Service Rating
4 AWG......2 AWG ......100 amps
1 AWG......2/0 ............150 amps
2/0............4/0 ............200 amps
400 kcmil..600 kcmil.....400 amps

NEC 384-13 All Circuit Overcurrent Devices shall be legibly identified as to purpose or use on a directory located on the face or inside of the electrical panel doors.

NEC 370-17 Raceways Containing Ungrounded Conductors No. 4 or larger enter a cabinet, box, or enclosure, the conductors shall be protected by a conduit bushing providing a smoothly rounded insulating surface.

Residential Electrical Code Examples for Services


IRC Codes

Home Electrical Service
1.A minimum of 100 Amp 3-wire service for a single-family dwelling unit. NEC 230.79

2.Only one service per dwelling, except for multiple occupancy buildings. NEC 230.2

3.Service disconnecting means shall be located at the point of entrance of the service conductors. 2003 IRC E3501.6.2

Electrical Disconnects
1.Exterior air units must have a disconnect within sight. NEC 440.14

2.Minimum disconnect rating for one circuit is 15 amps, for two circuits is 30 amps and for all others it is 60 amps. (detached garages with more than two circuits must have 60 amp wire) NEC 230.79

3.Electric water heaters shall have a disconnecting means within sight of the appliance or have a circuit breaker capable of being locked in the open position. NEC 430.III


General Information

1.Working space around electrical equipment shall be minimum: 30" wide and 36" deep and 6'-6" high. If the equipment is higher than 6'-6", the minimum height shall be to the top of the equipment. It also must be illuminated. 2003 IRC E3503

Always contact your local building authority for complete and up to date code information.

More about Electrical Codes for Services


related

Questions about Electrical Codes for Electrical Service Panels



Questions about Residential Electrical Wiring Codes for Main Services


Question from Willie, a Handyman in Newark, New Jersey

How is a Sub Panel Wired to a Main Service Panel?

I am adding a sub panel to my main panel in the basement. My problem is the main panel has two wire conductors with no ground, The neutral and ground bar are side by side in my main panel. The neutral wire runs through the neutral and touches the ground, But the sub panel I installed has a ground and neutral bar. So how can I connect a two wire black and neutral wire to a black, red, white, and ground in my sub panel?

Dave’s Answer:
Neutral and Ground Separation in a Sub Panel

The neutral bar is bonded to the ground only in the main panel. However, in a sub panel the neutral bar is separated and insulated from the ground and a separate neutral wire is required as part of the circuit feeding the sub panel. Additionally, a separate ground wire is required for the ground bar, which is bonded to the enclosure of the panel.


Question from Rob, a Handyman in Decatur Island, Washington

Installing a 200 amp Service Line

I am working on installing a 200 amp service line from a pad transformer (OPALCO-Orcas Power and Light) and meter base with a main disconnect out to my cabin which is approximately 250′ away, and into an Eaton 200 amp panel inside my cabin. I need to know the type of service wire I need (how many exactly, 3 or 4?) to put in the conduit in the trench and also the depth of the line, 18 or 24″ deep? I was told I need 4-0 wire (2 leads and a neutral) but I’ve also seen several diagrams with an added ground wire connecting the meter base and the panel, so that would mean 4 wires in the pipe. I was going to use 2.5″ Schedule 40 in the ditch and switch to 80 when it comes up and into the cabin. I was also planning to set two ground rods at the meter base (using 6 or 8 gauge copper wire?) and then another set of ground rods at the cabin for the panel itself. Would this work?


PLEASE NOTE:
To avoid redundancy, answers to most of these questions are available here on the website, or by obtaining a copy of the Home Electrical Wiring book.

IMPORTANT:
Electrical Panel Work of any kind should be done by a Licensed Electrical Contractor.



related

Join the Discussion!

Ask Your Electrical Code Question or Comment

Electrical Code Question
click here to ask a electrical code question
Comment
click here to leave a comment


»Avoid Costly Mistakes«
Wire It Right with the help of my Illustrated Wiring Book

Great for any Home Wiring Project,
Perfect for the Homeowner, Handyman, Electrician and Building Inspector.
Learn more about Residential Electrical Wiring Codes
Complete Guide to Home Electrical Wiring
Perfect for Homeowners, Students and Electricians
Includes:
Fully Illustrated
Home Electrical Wiring - Room by Room
Wiring 120 and 240 Volt Circuits
Wiring Main Panels
Underground and Overhead Services
Grounding and Bonding
55 Electrical Code Topics
6 Most Commonly Used Code Tables
11 Home Wiring Plans
Over 370 Photos
28 Wiring Diagrams and Illustrations
Illustrated Wiring Methods
Wiring Codes for Home Electrical Wiring
....and much more.

» Click here to learn more about Home Electrical Wiring «
  electrical wiring  



Top of Page